The ZONE GUARDIAN is a device which allows the mandatory quarterly testing of a wet-pipe
fire sprinkler system’s waterflow detector (flow switch) to be carried out remotely, saving both time and cost for end-users and fire sprinkler maintenance contractors.
The unit ensures zero wastage of water by the use of an artificial water flow created using a high-efficiency self-venting circulator pump manufactured by a global supplier.
The LPCB (Loss Prevention Certification Board) approved ZONE GUARDIAN is available in pipe sizes from 2"/50mm up to 6"/150mm and includes - as well as the circulator pump - a Potter VSR vane-type flow switch with adjustable retard and ball valves for vent, test and pump isolation, all mounted on 450mm long BS EN 10255 coated pipe with grooved connections each end.
We stock both left- or right-hand orientation, and the assembly may be installed horizontally (with flow switch on top) or vertically (with upward flow).
An electronic key-operated test module is included to allow testing of both the local and any interconnected waterflow detectors.
Zeffire Ltd are the exclusive distributor of the SEP ZONE GUARDIAN.